IS200TBAIS1C - Analog Input/Output Terminal Board

IS200TBAIS1C - Analog Input/Output Terminal Board IS200TBAIS1C - Analog Input/Output Terminal Board

World Of Controls understands the criticality of your requirement and works towards reducing the lead time as much as possible.

IS200TBAIS1C - Analog Input/Output Terminal Board is available in stock which ships the same day.

IS200TBAIS1C - Analog Input/Output Terminal Board comes in UNUSED as well as REBUILT condition.

To avail our best deals for IS200TBAIS1C - Analog Input/Output Terminal Board, contact us and we will get back to you within 24 hours.

SPECIFICATIONS

Part No.: IS200TBAIS1C
Manufacturer: General Electric
Product Type: Analog Input/Output terminal board
Series: Mark VIe

IS200TBAIS1C is a safety-certified Analog Input/Output terminal board. TBAI consists of 3 DC-37 pin connections for connecting to the I/O processors. A single connector is used to accommodate simplex applications (JR1). All three connectors are compatible with TMR applications. The input signals for the R, S, and T controls are fanned to the three connections in TMR applications.

  • TMR outputs aggregate the currents of the three connected output drivers and use a measuring shunt to calculate the overall current. The total current signal is then presented to the I/O processors for regulation to the requested setpoint.
  • TBAIS1C is a safety-certified product. In the Mark VIeS SIS, YAIC does not support the 200 mA output option. TMR applications can use the same terminal board.

IS200TBAIS1C Installation

The following analog I/O types can be accommodated by TBAI:

  • Analog input, two-wire transmitter;
  • Analog input, three-wire transmitter;
  • Analog input, four-wire transmitter;
  • 5 V, 10 V dc analog input
  • 0-20 mA analog output
  • 0-200 mA analog output

IS200TBAIS1C Operation

Each 24 V dc power output is rated for continuous output of 21 mA and is safeguarded against short circuit operation. The control system's 24 V dc supply can power the transmitters/transducers, or they can be powered separately. The JO jumper determines the current output type. Each output is monitored by diagnostics, and if a fault cannot be cleared by a command from the processor, a suicide relay in the I/O controller disconnects the relevant output.

Physical Characteristics

Fault detection

Monitor total output current. Check for hardware incompatibility using the connection ID chip.

Temperature range

-30°C to 65°C

Dimensions

10.16 cm wide by 33.02 cm tall

Diagnostics

  • The I/O controller interrogates each cable connector on the terminal board for its individual ID device.
  • The ID device is a read-only chip coded with the terminal board serial number, board type, revision number, and the JR, JS, JT connection location.
  • A hardware incompatibility fault is issued when the I/O controller reads this chip and finds a mismatch.

Configuration

The following are the options for jumpers:

  • Jumpers J1A through J8A allow you to choose between current and voltage input.
  • Jumpers J1B to J8B determine whether the return is linked to common or not.
  • Choose between 1 mA and 20 mA input current using jumpers J9A and J10A.


WOC experts are always available to help you with your Mark VIe requirements. For more information, please contact WOC.


FREQUENTLY ASKED QUESTIONS

 

How to Diagnostic Fault Detection IS200TBAIS1C?
Hardware limit checking based on customizable high and low values for 4-20 mA inputs, the health of D/A convert circuits, analog output current contribution monitoring, and suicide relay disconnects failing outputs in TMR set up to allow other two I/O packs to control

What is the DC Control Power of an I/O Pack?
28 V dc at 8 W control power per YAIC, with an additional 7 W available depending on the amount of 4-20 mA s used.