World Of Controls understands the criticality of your requirement and works towards reducing the lead time as much as possible.
IS200SSCA2AEC - Input/Output terminal board is available in stock which ships the same day.
IS200SSCA2AEC - Input/Output terminal board comes in UNUSED as well as REBUILT condition.
To avail our best deals for IS200SSCA2AEC - Input/Output terminal board, contact us and we will get back to you within 24 hours.
Part Number: IS200SSCA2AEC
Manufacturer: General Electric
Series: Mark VIe
Function: Simplex Serial Communication Input/Output (SSCA) terminal board
Number of channels: 6
Size: 15.9 cm high x 10.2 cm wide
Technology: Surface-mount
Temperature Operating: -30 to 65oC
Availability: In Stock
Country of Manufacture: United States (USA)
IS200SSCA2AEC is a Simplex Serial Communication Input/Output terminal board developed by General Electric. It is a part of GE Mark VIe system. It is a compact communication solution designed to support multiple channels of data transmission in industrial control systems. This board enhances communication capabilities, making it ideal for applications requiring robust and reliable serial connections.
WOC has the largest stock of Speedtronic control spares. Please contact our staff by phone or email for pricing and availability on any parts and repairs
What is IS200SSCA2AEC?
It is a Simplex Serial Communication Input/Output terminal board developed by General Electrics.
What signaling options are supported by the terminal board?
Each channel can be configured to support RS-232C, RS-485, or RS-422 signaling, allowing for flexibility and compatibility with various devices and systems.
How does the board integrate with the PSCA I/O pack?
The PSCA I/O pack plugs directly into the DC-37 pin connector on the SCA board, facilitating communication with the controller over an Ethernet network. This integration enhances data exchange and overall system connectivity.
What are the mounting options for the terminal board?
The terminal board can be mounted on a DIN-rail using a sheet metal carrier and plastic insulator mount. It can also be bolted directly into a cabinet, providing flexible installation options.
How should the shield termination be handled?
The I/O cable shield should be terminated on an external mounting bracket, which may be supplied by the customer or sourced from GE. Proper termination is essential for minimizing noise and ensuring reliable communication.
How do I ensure proper grounding for the board?
Mounting holes E1 and E2 are provided for chassis ground connections. One of the SCOM terminals (terminals 37-48) must be connected to a suitable shield ground to enhance signal quality and reliability.