World Of Controls understands the criticality of your requirement and works towards reducing the lead time as much as possible.
IS200SAIIH2ACD - Simplex Isolated Analog Input Terminal Board is available in stock which ships the same day.
IS200SAIIH2ACD - Simplex Isolated Analog Input Terminal Board comes in UNUSED as well as REBUILT condition.
To avail our best deals for IS200SAIIH2ACD - Simplex Isolated Analog Input Terminal Board, contact us and we will get back to you within 24 hours.
SPECIFICATIONS:
Part Number: IS200SAIIH2ACD
Manufacturer: General Electric
Series: Mark VIe
Product Type: Simplex Isolated Analog Input Terminal Board
Number of Channels: 12
Input Span: 1 - 5 V dc
Maximum lead resistance: 15 Ω maximum
Outputs: 24 V dc
Load on output currents: 800 Ω
AC Voltage Rejection: 60 V RMS
Voltage Range: 18 - 32 VDC
Mounting: DIN-rail mounting
Technology: Surface mount
Operating temperature: 30 to 65°C
Size: 15.9 cm high x 17.8 cm wide
Availability: In Stock
Country of Origin/Manufacturer: United States
Manual: GEH-6721_Vol_II
FUNCTIONAL DESCRIPTION:
IS200SAIIH2ACD is a Simplex Isolated Analog Input Terminal Board manufactured and designed by General Electric as part of the Mark VIe Series used in GE Speedtronic Turbine Control Systems. The Simplex Analog Input (SAII) terminal board is a compact analog input terminal board that accepts 10 analog inputs offers two analog outputs, and connects to the PAIC. The I/O pack plugs into the D-type connector and communicates with the controller over Ethernet. The 10 analog inputs accommodate 2-wire, 3-wire, 4-wire, or externally powered transmitters. Each analog input features point isolation when configured for externally powered devices. Each analog input has an isolator in the circuit with a rating of 1500 V rms. The two analog outputs are 0-20 mA but one can be jumper configured to 0-200 mA current when used with a PAICH2. High-density Euro-block type terminal blocks are used. An on-board ID chip identifies the SAII to the PAIC for system diagnostic purposes.
INSTALLATION:
The SAII plus a plastic insulator mounts on a sheet metal carrier that then mounts on a DIN rail. Optionally, the SAII plus insulator mounts on a sheet metal assembly and then bolts directly to a cabinet. There are two types of Euro-block terminal blocks available as follows:
OPERATION:
24 V dc power is available on the terminal board for all the transmitters (transducers). There is a choice of current or voltage inputs using jumpers. One of the two analog output circuits is 4-20 mA, and the other can be jumper configured for 4-20 mA or 0-200 mA. There is only one PAIC connection, so the terminal board cannot be used for TMR applications as with TBAI.
WOC has the largest stock of OEM Replacement Parts for GE Distributed Control Systems. We can also repair your faulty boards and supply unused and rebuilt boards backed up with a warranty. Our team of experts is available round the clock to support your OEM needs. Our team of experts at WOC is happy to assist you with any of your automation requirements. For pricing and availability on parts and repairs, kindly contact our team by phone or email.
What is the purpose of the Simplex Isolated Analog Input Terminal Board?
The Simplex Isolated Analog Input Terminal Board is designed to receive analog input signals while providing electrical isolation between the input signals and the control system, enhancing safety and signal integrity.
What types of signals can the terminal board handle?
The board can handle various analog signals, including voltage (e.g., 0-10V) and current (e.g., 4-20mA) inputs.
How is the isolation provided?
Isolation is typically achieved through the use of isolation amplifiers or transformers, which prevent ground loops and protect the control system from high voltages.