SPECIFICATIONS
Part No.: IS200DRLYH1AAA
Manufacturer: General Electric
Country of Manufacture: United States of America (USA)
Number of relay outputs: 12
Size: 21.59 cm long x 20.57 cm wide
Temperature: 0 to 60 oC
Product Type: Simplex Relay Output Board
Availability: In Stock
Series: Mark VI
Functional Description
IS200DRLYH1AAA is a Simplex Relay Output Board developed by GE. It is a part of Mark VI control system. The DRLY is meticulously engineered for DIN-rail mounting. Features 12 form-C dry contact output relays. Each relay is optimized to provide dependable switching capabilities, meeting the demands of various industrial and commercial applications.
Features
- Integration with Processor Boards: Seamlessly connects to either the VCCC or VCRC processor board via a single cable interface. This streamlined integration simplifies installation processes and ensures compatibility with existing systems, enhancing overall operational efficiency.
- Standardized Connectivity: Utilizing a 37-pin cable connector identical to those employed by the larger TRLY terminal board, the DRLY facilitates standardized connectivity across compatible systems. This uniformity enhances interchangeability and ease of equipment configuration, minimizing compatibility concerns.
- Expandability and Output Capacity: Two DRLY boards can be connected to a single VCCC or VCRC processor, effectively doubling the available contact outputs to a total of 24. This expandability ensures scalability and flexibility to accommodate evolving system requirements.
- Exclusively Simplex Configuration: Board is exclusively available in a simplex version, optimized to deliver reliable relay output functionality without unnecessary complexity. This specialization streamlines product selection and ensures compatibility with a wide range of applications.
Suppression Requirements
- External suppression equipment is expected to be provided by the customer.
- This equipment serves to mitigate electromagnetic interference and ensure the smooth operation of the relay output terminal board, safeguarding against potential disruptions caused by electrical noise.
Relay Response Time
- The relay response time is crucial for efficient operation.
- The board demonstrates an impressive response time, with a typical operating time of 15 milliseconds for activation and 10 milliseconds for release. This rapid response ensures swift switching capabilities, facilitating timely control and management of connected devices or systems.
Fault Detection
- The board incorporates robust fault detection mechanisms to enhance system reliability and facilitate timely troubleshooting.
- A green LED located at the top of the board monitors the state of the P28 V dc, providing a visual indicator of the board's operational status.
- Additionally, the voltage across each relay coil is indicated by a yellow LED, enabling quick identification of potential issues or abnormalities. It's noteworthy that while the board features comprehensive relay state monitoring, such monitoring is not present in the VCCC or VCRC, underscoring the importance of the fault detection features integrated into the board for ensuring system integrity.
- These fault detection features empower users to promptly identify and address any anomalies, minimizing downtime and optimizing system performance.
- By providing clear visual cues of the board's status and relay operations, the board enhances overall operational transparency and facilitates efficient maintenance practices, ensuring uninterrupted functionality in critical applications.
The WOC team is always available to help you with your Mark VI requirements. For more information, please contact WOC.
Frequently Asked Questions
What is IS200DRLYH1AAA?
It is a Simplex Relay Output Board developed by GE under the Mark VI series.
Does the board include suppression equipment for electromagnetic interference?
No, external suppression equipment is required and is expected to be provided by the customer. This equipment helps mitigate electromagnetic interference, ensuring smooth operation of the relay output terminal board.
What are the typical response times for relay activation and release ?
It demonstrates a typical response time of 15 milliseconds for activation and 10 milliseconds for release. This rapid response ensures efficient switching capabilities, facilitating timely control of connected devices or systems.
How does the board facilitate fault detection?
It features robust fault detection mechanisms, including LED indicators for monitoring the state of the P28 V dc at the top of the board. Additionally, yellow LEDs indicate the voltage across each relay coil, enabling quick identification of potential issues or abnormalities.
Is relay state monitoring available in the VCCC or VCRC?
No, relay state monitoring is not present in the VCCC or VCRC. However, the DRLY board provides comprehensive relay state monitoring, enhancing system reliability and facilitating timely troubleshooting.