IS230SAIIH4A - Simplex Analog Input Terminal Board

IS230SAIIH4A - Simplex Analog Input Terminal Board IS230SAIIH4A - Simplex Analog Input Terminal Board

World Of Controls understands the criticality of your requirement and works towards reducing the lead time as much as possible.

IS230SAIIH4A - Simplex Analog Input Terminal Board is available in stock which ships the same day.

IS230SAIIH4A - Simplex Analog Input Terminal Board comes in UNUSED as well as REBUILT condition.

To avail our best deals for IS230SAIIH4A - Simplex Analog Input Terminal Board, contact us and we will get back to you within 24 hours.

SPECIFICATIONS:

Part Number: IS230SAIIH4A
Manufacturer: General Electric
Series: Mark VIe
Product Type: Simplex Analog Input Terminal Board
Number of channels: 12 channels
Input span: 1 - 5 V dc
Outputs: 24 V dc
Generator current inputs: 0 to 5 A
Analog inputs Current inputs: 4-20 mA
Analog output current: 0-20 mA
Size: 15.9 cm high x 17.8 cm
Operating Temperature: -30 to +65°C
Frequency: 50 or 60 Hz
Repair: 3-7 Day
Availability: In Stock
Weight: 2 lbs
Country of Origin: United States
Manual: GEH-6721L

FUNCTIONAL DESCRIPTION:

IS230SAIIH4A is a Simplex Analog Input Terminal Board Manufactured and Designed by General Electric as part of the Mark VIe Series used in GE Distributed Turbine Control Systems. The Simplex Analog Input (SAII) terminal board is a compact analog input terminal board that accepts 10 analog inputs offers two analog outputs, and connects to the PAIC. The I/O pack plugs into the D-type connector and communicates with the controller over Ethernet. The 10 analog inputs accommodate 2-wire, 3-wire, 4-wire, or externally powered transmitters. Each analog input features point isolation when configured for externally powered devices. Each analog input has an isolator in the circuit with a rating of 1500 V rms. The two analog outputs are 0-20 mA but one can be jumper configured to 0-200 mA current when used with a PAICH2. High-density Euro-block type terminal blocks are used. An on-board ID chip identifies the SAII to the PAIC for system diagnostic purposes.

INSTALLATION:

The SAII plus a plastic insulator mounts on a sheet metal carrier that then mounts on a DIN rail. Optionally, the SAII plus insulator mounts on a sheet metal assembly and then bolts directly to a cabinet.

OPERATION:

24 V dc power is available on the terminal board for all the transmitters (transducers). There is a choice of current or voltage inputs using jumpers. One of the two analog output circuits is 4-20 mA, and the other can be jumper configured for 4-20 mA or 0-200 mA. There is only one PAIC connection, so the terminal board cannot be used for TMR applications as with TBAI.

WOC has the largest stock of GE Distributed Turbine Control System Replacement Parts. We can also repair your faulty boards. WORLD OF CONTROLS can also supply unused and rebuilt backed-up with a warranty. Our team of experts is available round the clock to support your OEM needs. Our team of experts at WOC is happy to assist you with any of your automation requirements. For pricing and availability on any parts and repairs, kindly get in touch with our team by phone or email.

FREQUENTLY ASKED QUESTIONS:

What is the Simplex Analog Input Terminal Board?

The Simplex Analog Input Terminal Board is a device used for connecting analog input signals to a control system or monitoring equipment.

What are analog input signals?

Analog input signals are continuous electrical signals that vary in voltage or current in response to changes in the physical environment, such as temperature, pressure, or flow rate.

What types of analog input signals can the Simplex Analog Input Terminal Board handle?

The Simplex Analog Input Terminal Board typically supports various types of analog signals, including voltage, current, temperature, pressure, and flow rate signals.