SPECIFICATIONS

Part No.: IS230STAI2ASRTD2AG01
Manufacturer: General Electric
Country of Manufacture: United States of America (USA)
Technology: Surface-mount
Temperature Operating: -30 to 65oC
Product Type: Analog I/O Terminal Board
Availability: In Stock
Series: Mark VIe

Functional Description

IS230STAI2ASRTD2AG01 is an Analog I/O Terminal Board developed by GE. It is a part of Mark VIe control system. This Simplex Analog Input (STAI) terminal board supports up to 10 analog inputs and 2 analog outputs, making it a versatile component for industrial control applications. It can connect to various types of transmitters and provides jumper-configurable analog outputs for flexible application requirements.

Features

  • Analog Input and Output Capabilities: The board supports 10 analog inputs (configurable for two-wire, three-wire, four-wire, and externally powered transmitters) and two analog outputs, with one capable of supporting 0-200 mA. The inputs can handle voltage ranges of ±5 V and ±10 V DC, making the board adaptable to various signal levels.
  • Configuration Flexibility: The board offers jumper-configurable options for selecting current or voltage inputs and adjusting output currents. Allows customization of input and output settings to meet specific control system requirements.
  • Simplex Design: The board is available only in a simplex form, which is designed for single, non-redundant applications rather than triple modular redundancy (TMR) setups.

Installation

  • The terminal board can be installed on a DIN rail with a sheet metal carrier and a plastic insulator. For mounting in an equipment cabinet, the insulator and carrier can also be attached directly to a metal assembly.
  • The board comes with two types of Euro-block terminal blocks, each with 48 terminals
    Includes a right-angle header for connecting various pluggable terminal blocks with 48 terminals.

Supported Analog Connections

  • Two-wire, three-wire, and four-wire analog input transmitters.
  • Externally powered analog input transmitters.
  • Voltage inputs with ranges of ±5 V and ±10 V dc.
  • Analog outputs with ranges of 0-20 mA and 0-200 mA (jumper configurable).

Operation

The board is designed to supply 24 V dc power to connected transmitters. It allows for selectable current or voltage inputs through jumper settings, which provide the following functionalities:

  • Current/Voltage Selection: Inputs can be configured for either current or voltage signals, depending on jumper settings.
  • Output Range Adjustment: The two analog output circuits can be adjusted via jumpers for 4-20 mA or 0-200 mA output, depending on application needs.
  • Single Cable Connection: Due to its design, the STAI board does not support TMR applications and is intended for simplex use only.

Configuration

The configuration of the terminal board is achieved through jumper settings. Below is a breakdown of jumper configurations for various input and output options:

  • Jumpers J1A through J8A are used to select between current and voltage input for the first eight analog inputs.
  • Jumpers J1B through J8B determine whether the return path for inputs is connected to a common return or remains open.
  • Jumpers J9A and J10A allow for setting the input current range between 1 mA and 20 mA.
  • Jumper J0 configures Output 1 for either a 20 mA or 200 mA output current.

The WOC team is always available to help you with your Mark VIe requirements. For more information, please contact WOC.

Frequently Asked Questions

What is IS230STAI2ASRTD2AG01?
It is an analog I/O terminal board developed by GE under the Mark VIe series.

How is the board installed?
The board is mounted on a DIN rail with a sheet metal carrier and a plastic insulator. Alternatively, it can be mounted directly to a metal assembly in a cabinet. It features Euro-block terminal blocks with 48 terminals for secure wiring connections.

How can I configure the board for current or voltage inputs?
Jumpers J1A through J8A select current or voltage input for the first eight analog inputs. Jumpers J1B through J8B allow configuration for a common or open return path for these inputs.

Can I use the board in TMR (Triple Modular Redundancy) applications?
No, the board is only designed for simplex applications and does not support TMR configurations.

How are the analog output ranges configured?
The board includes a jumper setting (Jumper J0) that allows Output 1 to be adjusted for either 20 mA or 200 mA output, depending on the application requirements.