IS220PPRFH1B - PROFIBUS Master Gateway I/O Module

IS220PPRFH1B - PROFIBUS Master Gateway I/O Module IS220PPRFH1B - PROFIBUS Master Gateway I/O Module

World Of Controls understands the criticality of your requirement and works towards reducing the lead time as much as possible.

IS220PPRFH1B - PROFIBUS Master Gateway I/O Module is available in stock which ships the same day.

IS220PPRFH1B - PROFIBUS Master Gateway I/O Module comes in UNUSED as well as REBUILT condition.

To avail our best deals for IS220PPRFH1B - PROFIBUS Master Gateway I/O Module, contact us and we will get back to you within 24 hours.

SPECIFICATIONS

Part No.: IS220PPRFH1B
Manufacturer: General Electric
Product Type: PROFIBUS Master Gateway I/O Module
Country of Manufacture: United States (USA)
Series: Mark VIe

IS220PPRFH1B is a PROFIBUS Master Gateway I/O Module developed by GE under Mark VIe series. It is a PROFIBUS DPV0, Class 1 master that maps Mark VIe controllers on the I/O Ethernet to I/O from PROFIBUS slave devices. The module includes a processor board that is shared by all Mark VIe distributed I/O modules and an acquisition carrier board that is equipped with a Hilscher GmbH-provided COM-C PROFIBUS communication module.

IS220PPRFH1B Features

  • A PROFIBUS RS-485 interface is provided by the COM-C module through a DE-9 D-sub receptacle connector. It functions as a PROFIBUS DP master, supporting up to 125 slaves with 244 bytes of inputs and outputs each with transmission rates ranging from 9.6 KBaud to 12 MBaud.
  • The following redundancy options are supported by the PPRF:
    • A single I/O Ethernet connection for a single I/O pack (no redundancy)
    • A single I/O pack with two Ethernet connections for the I/Os
    • Hot-backup Ethernet connections with two ports
  • Other IO packs share the twin I/O Ethernet connection design. However, two PPRFs are used in the hot-backup system, one of which is active and connecting with slave devices via PROFIBUS and the other of which is passive and in standby mode, ready to take over in the case of an active master failure.

Compatibility

The PPRF is mounted on the PROFIBUS Master Gateway Terminal board (SPIDG1A), which also provides an electronic ID. As the PROFIBUS connection is connected to the DE-9 D-sub receptacle connector exposed on the side of the PPRF, the interface to the PPRF is the sole connection it has. Indicator LEDs on the PPRF give visual diagnostics. The number of I/O packs utilized in a signal path is referred to as the control mode:

  • One I/O pack and one or two network connections are used by Simplex.
  • Two I/O packs with two network connections each are used in hot-backup.

IS220PPRFH1B Operation

Processor

The I/O pack or module function-specific acquisition board is connected to the processor board. The soft-start circuit ramps up the voltage available on the processor board when input power is applied. The processor reset is turned off and the local power supply are turned on in order. After finishing self-test routines, the processor loads application code from flash memory that is particular to the I/O pack or module type. To verify that the application code, acquisition board, and terminal board are correctly matched, the application code reads the board ID information.

PROFIBUS Gateway Hardware

The PROFIBUS DP (Decentralized Periphery) feature is implemented by firmware in the PPRFs COM-C module, which is based on Siemens ASPC2 technology. The PPRF only offers the fundamental DPV0 capability, which includes configuring slave devices, cyclically exchanging I/O data with them, and receiving PROFIBUS diagnostics, despite the fact that the COM-C module is DPV1 capable.

Data Flow between PPRF and Controller

Fixed I/O and PROFIBUS I/O are the two types of data flow that go between the PPRF and the controller. The few inputs and outputs that are fixed include those that are shared by all I/O packs, including L3DIAG and IOPackTmpr, but there are no application-driven outputs. The PPRF firmware contains a predefined set of fixed I/O. According to the hardware configuration supplied by the application, PROFIBUS I/O is defined as the data exchanged between PROFIBUS slave devices.

IS220PPRFH1B Specifications

PROFIBUS Master type
DPV0 Class 1 master

PROFIBUS connection
Connector for the DE-9 D-sub RS-485 interface

Number of slaves
125 slaves, each capable of handling 255 bytes of inputs and outputs

I/O throughput
Half Boolean and half analog, 500 inputs and 500 outputs, 40 ms frame rate (This is a requirement, not a hard limit)

The WOC team is always available to help you with your Mark VI requirements. For more information, please contact WOC.

 

Frequently Asked Questions

 

What is IS220PPRFH1B?
IS220PPRFH1B is a PROFIBUS Master Gateway I/O Module developed by GE under Mark VIe series.

What is the ambient temperature rating?
The ambient temperature rating is from -20 to +55 degrees Celsius.

What is the input current rating of the module?
Max 18 Adc is the input current rating.

What is the nominal input voltage rating?
28Vdc is the nominal input voltage.

How to Obtain IS220PPRFH1B?