SPECIFICATIONS
Part Number: 5501-428
Manufacturer: Woodward
Product type: Actuator Controller Module
Size: 10.25 x 9.75 x 1 in
Dither Current: 25 Hz, 25% duty cycle
LED: Red
Output Current Tolerance: ±1% of full scale
Current: 10mA
Availability: In Stock
Country of Manufacture: United States (USA)
Functional Description
5501-428 is a Netcon Actuator Controller Module developed by Woodward. It is a controller module, belonging to the renowned NetCon Controllers Series by Woodward. This module is specifically designed to cater to the precise needs of industries where precise control of proportional or integrating, pneumatic or hydromechanical actuators is essential.
Features:
- Features two independent channels, allowing simultaneous control of two different actuators. This dual-channel capability enables efficient and coordinated control of multiple actuators in various industrial applications.
- With both proportional and integrating control capabilities, the controller ensures precise and dynamic actuator positioning. This feature is particularly beneficial in processes that require fine-tuning and continuous adjustments for optimal performance.
- Compatible with both pneumatic and hydromechanical actuators, broadening its applicability across a wide range of systems and industries. This versatility allows seamless integration into diverse industrial processes.
- Programmable Error Thresholds: This functionality empowers users to define specific tolerance levels for the actuator's response, ensuring that it operates within desired limits. This capability is crucial for achieving precision and stability in critical processes.
- Designed with a user-friendly interface, making it easy to configure and operate. It may offer features like a graphical display, intuitive menus, and straightforward programming options, streamlining the setup and maintenance processes.
- Support various communication protocols, enabling seamless integration with supervisory control and data acquisition (SCADA) systems. This allows operators to monitor and control the actuators remotely, adding convenience and accessibility to the process.
Product Attributes
- It is available in the 10mA version, and its power requirements are listed as +5 V @ 0.5 A and +24 V @ 1 A. The part number of the model indicates its maximum output current capability, with various versions available in the series. It , has a Current Output Tolerance of ±1% of full scale and a Current Read Back Tolerance of ±5% of full scale.
- For each actuator channel on the module, there is an option to have one or two position feedback devices, such as LVDT or RVDT. The module is equipped with several fault detection features, including alarms for feedback, excitation, and driver-related errors.
- To install the module securely, it is placed into a card guide within the control's chassis, where it connects to the motherboard. When disconnecting the motherboard, the module can be easily removed using the two handles located at the top and bottom. It requires a MicroNet low-density discrete (gray) cable for proper functioning, and the use of analog (black) cables should be avoided.
- For detailed information about the Module, including specifications and installation instructions, including field-wiring information, users can refer to the MicroNet Simplex and MicroNet Plus Manual 26166V2, which is available online.
- It's worth mentioning that in a control system with multiple 2 CH Actuator modules , there is a possibility of a 'beat' frequency being created around 3000 Hz. This signal may generate noise within the chassis and cause fluctuations in low amplitude signals, such as those from RTDs and thermocouples. Users should be aware of this phenomenon and take appropriate measures to mitigate any potential issues caused by this 'beat' frequency.
World of Controls has the most comprehensive selection of GE and Woodward components. Our professionals are available to help you with your requirements at any time. If you require any additional information, please contact WOC immediately.
Frequently Asked Questions
What is 5501-428?
It is an Actuator Controller Module developed by Woodward.
How many position feedback devices can be used for each actuator channel?
Each actuator channel on Model may have one or two position feedback devices. Common options include LVDT and RVDT.
What fault detection features does Model have?
Model is equipped with several fault detection features, including alarms for errors related to feedback, excitation, and drivers. These features enhance the module's reliability and ensure safe operation.
How is the module secured in the control's chassis?
The module is secured into a card guide within the control's chassis, where it plugs into the motherboard. To disconnect the motherboard, the module can be easily removed using two handles, located at the bottom and top.
What type of cable does the module require?
It requires a MicroNet low-density discrete (gray) cable for proper functioning. It is essential to avoid using analog (black) cables for this module.
Where can I find more information about the Actuator Control Module, including specs and installation instructions?
Detailed information about the Actuator Control Module, including specifications and installation instructions, can be found online in the MicroNet Simplex and MicroNet Plus Manual 26166V2.