531X307LTBAFG1 - LAN Terminal Board

531X307LTBAFG1 -  LAN Terminal Board 531X307LTBAFG1 -  LAN Terminal Board

World Of Controls understands the criticality of your requirement and works towards reducing the lead time as much as possible.

531X307LTBAFG1 - LAN Terminal Board is available in stock which ships the same day.

531X307LTBAFG1 - LAN Terminal Board comes in UNUSED as well as REBUILT condition.

To avail our best deals for 531X307LTBAFG1 - LAN Terminal Board, contact us and we will get back to you within 24 hours.

SPECIFICATIONS

Part No.: 531X307LTBAFG1
Manufacturer: General Electric
Product Type: LAN Terminal Board
Series: EX2000

531X307LTBAFG1 is a EX2000 LAN Terminal Board developed by GE. The component provides an interface between control devices and devices such as, contactors, indicator lights,
pushbuttons, and interlocks etc.

I/O Terminal Wiring

Size 28 14 AWG wire is required for all I/O terminals.

  • A 26-conductor ribbon cable can be as long as 20 feet.
  • Depending on the application, input and output wiring might be as long as necessary.

LED Indicators

  • When a source is applied to circuits IN1 through IN8, respectively, LED indicators LED1 through LED8 turn on.
  • LED17 and LED23 turn on when relays RX1 through RX7 are activated.

531X307LTBAFG1 Input Specifications

The following requirements for input voltage and current apply to terminals IN1 through IN8:

  • 4 -10 mA peak at 24- 230 V ac, 60 Hz (G1)
  • 24- 250 V dc (G1 and G2): 4- 8 mA 115 230 V ac, 50 Hz (G1): 4 -10 mA peak

Procedure to Replace 531X307LTBAFG1 

  1. Turn off the drive's power and let all the capacitors some time to drain. To make sure the power is off, test any electrical circuits before handling them.
  2. To reach the board, open the drive's cabinet door. (The LTB is normally found underneath the board rack of the drive.)
  3. Carefully detach all cables from the LTB board in the manner shown below:
    1. Take hold of the cable connectors on either side that mates with the board connector when using ribbon cables.
    2. then carefully remove the cable connector.
    3. Pull the tab slowly if there are pull tabs on the cords.
    4. To release wires that are fastened to terminals, remove the screw at the top of each terminal and take each wire out with care. (Be sure to name the wires to make reconnection easier.)
  4. Take out the four screws holding the LTB to the standoffs, then take out the board.
  5. Install the new board on the four standoffs using the four screws that were removed in step 4 and orient the new LTB in the same location as the one that was removed.
  6. Reattach all cables that were cut off in step 3, making sure that each connector is positioned correctly on both ends.
  7. Reconnect each individual wire that was cut off in step 3 (as indicated by labeling), making sure that each wire is securely fastened in the terminal.

The most extensive assortment of EX2000 replacement components can be found at World of Controls. Our experts are here to assist you with your requirements at any time. Please contact WOC if you require any additional information.

 

Frequently Asked Questions

 

What is 531X307LTBAFG1?
531X307LTBAFG1 is an EX2000 LAN Terminal Board developed by GE

How to Obtain 531X307LTBAFG1?
WOC provides 531X307LTBAFG1 as well as other turbine control products. Contact World of Controls.